漢偉股份有限公司
漢偉股份有限公司
Features
• Uses Echelon® LONWORKS® network (E-Bus) protocol.
• Free Topology Transceiver (FTT) high speed 78 kilobit communications network.
• Compliant with VAV Device Object Type number 8010 functional LONMARK® profile.
• Capable of stand-alone operation, but can also use E-Bus network communications.
• 120 controllers per Q7750A Excel 10 Zone Manager.
• Easy user access to the E-Bus network communications jack.
• Designed for Pressure Independent or Pressure Dependent Single or Dual Duct Variable Air Volume (VAV) and Constant Volume Air Terminal Unit control.
• Uses a Microbridge air flow sensor with patented dual integral restrictor design.
• Easy user access to air flow sensor inputs.
• Provides Proportional Integral Derivative (PID) temperature control.
• Energy saving setpoint reset for electrical demand limit control.
• Floating or modulating hot water or three-stage electric heat.
• Series or induction fan control.
• Provides patented nonlinear floating algorithm for velocity control loops.
• Individual zone pressurization for supply and exhaust control.
• Factory configured via EEPROM with critical user parameter default values.
• Supports motion sensor interface for enhanced energy savings.
• Supports Terminal Regulated Air Volume (TRAV) concept.
• Supports pressurize and depressurize, night purge, and morning warm-up sequences.
• Both plastic housing and controller module wiring subbase are UL 94-5V rated (W7751D,F).