漢偉股份有限公司
漢偉股份有限公司
Features
• LONMARK® HVAC profile #8020
• Stand-alone operation or on high-speed 78 kilobit Echelon® LONWORKS© network
• Uses Echelon LonTalk® protocol
• FTT10A Transceiver
• Direct connection of thermal actuators
OTE: VC6983 generates high-voltage pulses in the end position and therefore cannot be used in conjunction with the W7754.
• Direct connection to fan switch
• Direct and indirect connection to electrical heat Supports (via relays) staged fan (up to 3 stages) or (via 0…10 V output) variable-speed fan
• Factory-configured default parameters
• Wide range of supported valves and actuators
• Supports (via 0…10 V output) one proportional valve or a 6-way valve for heat/cool chilled ceilings (alternatively to variable-speed fan)
• Interlocks and time delays to protect equipment
• Connected floating actuators exercised once a week
• Slim design fits into narrow fan coil units
• Terminals all on one side allow controllers to be positioned at back of fan coil unit
• Power supplied by power mains or 24 V